12.11.3 Brake Chopper Ratings for Mains Voltage 525–690 V
Table 68: Brake Chopper Ratings for VACON
®
NXP IP00 Drive Modules, Mains Voltage 525–690 V, 50/60 Hz, 3~
The minimum brake resistance [Ω]
Brake power @1166 V DC [kW]
(1)
1
When using recommended resistor types. Peak power capability of the brake chopper can be calculated with DC-link voltage (Udc) and brake
resistor resistance Rb by Udc
2
/Rb.
12.12 Faults and Alarms
12.12.1 Fault 1 - Overcurrent, Subcode S1 - Hardware trip
Cause
There is too high a current in the motor cable. Its cause can be 1 of the following:
A sudden heavy load increase
A short circuit in the motor cables
The motor is not the correct type
Troubleshooting
Check the load.
Check the motor.
Check the cables and connections.
Make an identification run.
AQ351737303996en-000201 / DPD00888 | 151Danfoss A/S © 2023.09
Specifications
VACON® NXP IP00 Drive Modules
Operating Guide