EasyManua.ls Logo

Danfoss VACON NXP IP00 - Fuse Sizes for 525-690 V AC, 12-Pulse

Danfoss VACON NXP IP00
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 53: Fuse Sizes (Bussmann) for 525–690 V AC, FR13–FR14, 6-pulse
Enclo-
sure size
Drive
type
Fuses with flush end contact
(metric)
Fuses with flush end contact
(US)
Fuse In [A]
DC fuses
per drive
AC fuses
per drive
Fuse part nr. (aR)
(AC/DC)
Fuse size
Fuse part nr.
(aR)
Fuse size
FR13
920
170M6466 (AC)
170M8610 (DC)
3BKN/50
3BKN/75
170M6566 (AC)
3GKN/50
1250
1000
4
6
1030
170M6466 (AC)
170M8610 (DC)
3BKN/50
3BKN/75
170M6566 (AC)
3GKN/50
1250
1000
4
6
1180
170M6466 (AC)
170M8610 (DC)
3BKN/50
3BKN/75
170M6566 (AC)
3GKN/50
1250
1000
4
6
FR14
1500
170M6466 (AC)
170M8610 (DC)
3BKN/50
3BKN/75
170M6566 (AC)
3GKN/50
1250
1000
6
9
1900
170M6466 (AC)
170M8610 (DC)
3BKN/50
3BKN/75
170M6566 (AC)
3GKN/50
1250
1000
8
12
2250
170M6466 (AC)
170M8610 (DC)
3BKN/50
3BKN/75
170M6566 (AC)
3GKN/50
1250
1000
8
12
Table 54: Fuse Sizes (Ferraz Shawmut) for 525–690 V AC, FR10–FR12, 6-pulse
Enclo-
sure size
Drive
type
Fuse
size
DIN 43620
DIN 43653 (80
mm)
DIN 43653 (110
mm)
Threaded end
contacts (metric)
Fuse In
[V]
Fuses
per drive
FR10
261
2
2 PV 0700
32 D08A 0700
32 D11A 0700
32 TTF 0700
700
3
325
2
2 PV 0700
32 D08A 0700
32 D11A 0700
32 TTF 0700
700
3
385
2
2 PV 0700
32 D08A 0700
32 D11A 0700
32 TTF 0700
700
3
416
3
3 PV 1000
33 D08A 1000
33 D11A 1000
33 TTF 1000
1000
3
FR11
460
3
3 PV 1000
33 D08A 1000
33 D11A 1000
33 TTF 1000
1000
3
502
3
3 PV 1000
33 D08A 1000
33 D11A 1000
33 TTF 1000
1000
3
590
2
2 PV 0700
32 D08A 0700
32 D11A 0700
32 TTF 0700
700
6
FR12
650
2
2 PV 0700
32 D08A 0700
32 D11A 0700
32 TTF 0700
700
6
750
2
2 PV 0700
32 D08A 0700
32 D11A 0700
32 TTF 0700
700
6
820
3
3 PV 1000
33 D08A 1000
33 D11A 1000
33 TTF 1000
1000
6
FR12 DC-
link
(1)
2
NA
NA
12.5 URD 72D11A
0500
12.5 URD 72 TTF
0500
500
()
2
1
In FR12 (12-pulse drive) or in FR12 (6- or 12-pulse) with internal brake, the DC-links between units are connected together. If connected together,
there must be DC-link fuses in DC-minus and DC-plus poles between the units. (In 6-pulse drive without internal brake, DC-links between units are
separate and there is no need for fuses.)
Fuse Un=1000V/1250V
12.4.8 Fuse Sizes for 525–690 V AC, 12-pulse
The aR fuses are thermally rated into switch fuse in 50 °C (122 °F) ambient temperature.
AQ351737303996en-000201 / DPD00888 | 139Danfoss A/S © 2023.09
Specifications
VACON® NXP IP00 Drive Modules
Operating Guide

Table of Contents

Related product manuals