Danfoss VACON NXP IP00 - Power Ratings for Mains Voltage 380-500

Danfoss VACON NXP IP00
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
e30bg038.10
I
L
I
L*110%
1 min
9 min
I
t
I
L*110%
Illustration 91: Low Overload
The high overload means that if 150% of the continuous current (I
H
) is required for 1 minute every 10 minutes, the remaining 9
minutes must be approximately 92% of I
H
or less. This is to make sure that the output RMS current is not more than I
H
during the
duty cycle.
e30bg039.10
I
H
I
H*150%
1 min 9 min
I
H*150%
I
t
Illustration 92: High Overload
For more information, refer to the standard IEC61800-2.
12.9.2 Power Ratings for Mains Voltage 380–500 V
Table 63: Power Ratings in Mains 380–500 V, 50/60 Hz, 3~
Enclo-
sure size
Drive type
Loadability
(1)
Motor shaft power
Low
High
400 V supply
500 V supply
Rated
continu-
ous cur-
rent I
L
(A)
(2)
Rated
over-
load
current
(A)
Rated
continu-
ous cur-
rent I
H
(A)
Rated
over-
load
current
(A)
Max
current
I
S
Low
over-
load P
(kW)
High
over-
load P
(kW)
Low
over-
load P
(kW)
High
over-
load P
(kW)
FR8
NXP0140 5
140
154
105
158
210
75
55
90
75
NXP0168 5
170
187
140
210
280
90
75
110
90
AQ351737303996en-000201 / DPD00888144 | Danfoss A/S © 2023.09
Specifications
VACON® NXP IP00 Drive Modules
Operating Guide