3.
4.
5.
6.
7.
- a.
- b.
- c.
- d.
Open the power unit cover.
e30bg032.10
Pull the cable through the bottom plate of the cabinet and fix the PE conductor to the PE busbar of the cabinet.
Route the motor phase conductors through common mode chokes. See 6.5 Common-mode Chokes on Motor Cables.
To make a 360° connection with the grounding clamp for cable shield, expose the shield of motor cables.
e30bk616.10
1
2
4
3
Illustration 28: Installing EMC Grounding
1
PE busbar
2
Grounding clamp
3
Cable clamp
4
Exposed cable
Connect the cables. See the correct tightening torques in 12.8 Tightening Torques of the Terminals.
Connect 3 power cables to the input terminals of the power unit. It is recommended to use cables designed for 90
°C (194 °F). Connect the L1 cable to the L1 input terminal of the power unit, the L2 cable to the L2 terminal, and the
L3 cable to the L3 terminal.
Connect 3 motor cables to the output terminals U, V, and W of the power unit.
Connect the control cables. See 7 Control Unit for more information on control cables.
Make sure that the control cable wires do not come in contact with the electronic components of the unit or
control components inside the cabinet.
Attach the grounding conductor of each cable to the PE busbar.
AQ351737303996en-000201 / DPD00888 | 53Danfoss A/S © 2023.09
Electrical Installation
VACON® NXP IP00 Drive Modules
Operating Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VACON NXP IP00 and is the answer not in the manual?

Danfoss VACON NXP IP00 Specifications

General IconGeneral
BrandDanfoss
ModelVACON NXP IP00
CategoryControl Unit
LanguageEnglish

Related product manuals