Status text Description
BTB in operation The bus tie breaker is closed.
Busbar OK in -
remaining time
Displays the remaining time (in seconds)
before the emergency genset begins the
emergency genset stop procedure after a
blackout is solved.
Cooldown - remaining
time
Displays the remaining time (in seconds)
for the genset cooldown.
Crank off
There is no running detection of the
genset during the genset start procedure,
and the crank is turned off.
Crank on
The crank is activated in order to start the
genset.
De-loading SCB /
SGB / BTB
The controller is busy de-loading the
external breaker to open the external
breaker.
De-loading GB
The controller is busy de-loading the
generator breaker to open the generator
breaker.
De-loading SGB
The controller is busy de-loading the shaft
generator breaker to open the shaft
generator breaker.
Dividing section
The controller is busy de-loading the bus
tie breaker to open the bus tie breaker.
Engine stopping The genset is being stopped.
Engine test -
remaining time
Displays the remaining time (in seconds)
that the EMERGENCY genset controller
engine test is still active for.
Fixed power
The shaft generator or shore connection is
running base load and the genset is
connected to the busbar.
Frequency regulation
The genset is running and is being
regulated using frequency regulation.
Frequency too high
The genset frequency is too high and
should be adjusted to a lower value. The
adjustment happens automatically if the
controller is under PMS control.
Frequency too low
The genset frequency is too low and
should be adjusted to a higher value. The
adjustment happens automatically if the
controller is under PMS control.
Harbour operation
The emergency genset is operating in
harbour operation and supplies power to
the busbar as the first priority genset.
Idle run - remaining
time
Displays the remaining time (in seconds)
that the genset is running before the
genset continues with the genset start or
stop procedure.
PPM 300 Operator's manual 4189340910 UK
www.deif.com
Page 14 of 157