13.3 Troubleshooting alarms
13.3.1 Troubleshooting alarms
The system has many pre-configured and configurable alarm protections. Activated alarms require action to resolve the
problem in the system. An active alarm typically has an active alarm protection which is designed to protect the system and
equipment.
See Alarms and log for more information about how alarms can be actioned.
13.3.2 Troubleshooting analogue input sensor failures
Below range alarm
The analogue input measurement is below the configured set point.
Analogue input type Possible root cause(s)
Current
Wire break
High resistance
Voltage
Wire break
Short circuit to ground
Resistance Short circuit
Above range alarm
The analogue input measurement is above the configured set point.
Analogue input type Possible root cause(s)
Current Short circuit
Voltage Short circuit to supply
Resistance Wire break
13.4 Engine
13.4.1 Start failure
Alarm
Start failure.
Configuration
Configure > Parameters > Engine > Start sequence > Start failure