Loading...
Possible cause(s) Fuel supply to engine.
Engine has reached the maximum number of start attempts configured.
Engine failure (electrical/mechanical).
Checks and
recovery
Check fuel supply line.
Check start attempts configuration
Configure > Parameters > Engine > Start sequence > Start attempts
Engine starter battery
13.4.2 Overspeed #
INFO
This applies to both Overspeed 1 and Overspeed 2 alarm protections.
Alarm
Overspeed #
Configuration
Configure > Parameters > Engine > Protections
Possible cause(s) Engine speed rating is incorrect.
Incorrect engine speed controller setting.
Checks and
recovery
Check the rated speed of the engine.
Adjust the speed controller if necessary.
13.5 Network and communication
13.5.1 Ethernet redundancy broken
Alarm
Ethernet redundancy broken
Configuration
Configure > Parameters > System power management > Network
Possible cause(s) System never had a redundant Ethernet connection.
The existing redundant Ethernet connection has become unplugged, damaged or faulty.