Appendix B - JVL6-32 Residual Current Circuit
Breaker_01/2016
- 88 -
APPENDIX A - CONTROLLER POWER CONSUMPTION: CURRENT INLET
Apparent power (S)
measured in VA
The “Power triangle”
Impedance
phase angle
True power (P)
measured in Watts
Reactive power (Q)
measured in VAR
P = true power
P
u(t) x i(t)dt
1
T
0
T
measured in units of Watts
where T is the period of the signal
On a CVI3, the Power peak is 5kW.
To dimension an installation, the apparent power consumption is the only needed information.
S = apparent power
S U
rms
x I
rms
measured in Volt-Amps (VA)
The apparent power peak is 6kVA the duration of the peak is < 0.5 s
The mean apparent power is always ≤ 1 kVA.
SINGLE PHASE 230 V
At 230 V
I
rms
x
1 kVA
A
230
2
I
rms
1000 x
230
2
I
rms
6.15 A
Then we recommend to use a circuit breaker 10A Curve D.
At 110 V
I
rms
x
1 kVA
A
110
2
I
rms
1000 x
110
2
I
rms
12.85 A
Then we recommend to use a circuit breaker 20A Curve D.

Table of Contents

Other manuals for Desoutter CVI3 Vision

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Desoutter CVI3 Vision and is the answer not in the manual?

Desoutter CVI3 Vision Specifications

General IconGeneral
BrandDesoutter
ModelCVI3 Vision
CategoryController
LanguageEnglish

Related product manuals