EasyManua.ls Logo

Eaton easy500, easy700

Eaton easy500, easy700
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 Wiring  with
4.8 Weekly timer
Operating instructions 05/10 MN05013003Z-EN www.eaton.com 117
4.8.3.4 Time overlaps example
The time settings of a time switch overlap. The clock switches on at 16:00
on Monday, whereas on Tuesday and Wednesday it switches on at 10:00.
On Monday to Wednesday the switching-off time is 22:00.
Figure 62: Time overlaps signal diagram
4.8.3.5 Power failure example
The power is removed between 15:00 and 17:00. The relay drops out and
remains off, even after retriggering of the power supply, since the first break
time was at 16:00.
4.8.3.6 24 hour switching example
The time switch is to switch for 24 hours. Switch-on time at 00:00 on
Monday and switch-off time at 00:00 on Tuesday.
On and off times always follow the channel which switches
first.
Ö4 A +
D MO-MI
ON 16:00
OFF 22:00
Ö4 B +
D TU-WE
ON 10:00
OFF 00:00
When it is switched on, easy always updates the switching
state on the basis of all the available switching time settings.
Ö4 A +
D MO-SU
ON 12:00
OFF 16:00
Ö4 B +
D MO-SU
ON 12:00
OFF 18:00
Ö1 A +
D MO
ON 00:00
OFF --:--
Ö1 B +
D TU
ON --:--
OFF 00:00