2 Installation
2.3 Ter minations
Operating instructions 05/10 MN05013003Z-EN www.eaton.com 29
2.3 Terminations
2.3.1 Tools
Slot-head screwdriver, width 3.5 mm, tightening torque 0.6 Nm.
2.3.2 Cable cross-sections
• Solid: 0.2 to 4 mm
2
• Flexible with ferrule: 0.2 to 2.5 mm
2
2.4 Connecting the power supply
2.4.1 Cable protection
Connect on easy a cable protection (F1) rated for at least 1 A (slow).
2.4.2 Supplying AC basic units
EASY…-AB-RC(RCX), EASY…-AC-R(RC, RCX)
Figure 7: Supply voltage to AC basic unit
→
The required connection data for device types,
easy-AB with 24 V AC, easy-AC with standard voltages of
100 V AC up to 240 V AC, easy-DA with 12 V DC and easy-DC
with 24 V DC are provided in the (→ section “8.3 Technical
data”, page 210).
The easy500 and easy700 basic units run a system test for two
seconds after the power supply has been switched on. Either
RUN or STOP mode will be activated after these two seconds,
depending on the default setting.
→
When easy is switched on for the first time, its power supply
circuit behaves like a capacitor. Ensure that reed relay contacts
or proximity switches are not used as the switching device for
switching on the power supply.