4 Wiring  with
4.4 Analog value comparator/threshold value switch
84 Operating instructions 05/10 MN05013003Z-EN www.eaton.com
4.4.1 Circuit diagram display with analog value comparator
Analog value comparators are integrated as contacts in the circuit diagram.
In the circuit diagram above, I1 enables both analog value comparators. If a
value goes below the set value, A1 switches output Q1. If another value
exceeds the set value, A2 deactivates output Q1. A3 switches marker M1 on
and off.
Table 12: Parameter display and parameter set for analog value comparator:
4.4.2 Compatibility with 400 with500 and 600 with 700
New functions have been added to the parameter display of easy500 and
easy700. The easy400 and easy600 parameters can be found at the
following points.
I1uA1----SQ1
hA2----RQ1
A3-------ÄM1
A1 EQ +
I1 +0 Æ
F1 +0
I2 +0 æ
F2 +0
OS +0
HY +0
A1 Analog value comparator function relay 1
EQ Equal mode
The function relay has the following modes:
LT: less than
LE: less than/equal to
EQ: equal to
GE: greater than/equal to
GT:greater than
+ + appears in the PARAMETER menu.
- does not appear in the PARAMETER menu
I1 Comparison value 1 (positive value I7, I8, I11, I12, actual value T1 to T16, C1 to C16)
F1 Gain factor for I1 (I1 = F1 x actual value at I1); F1 = positive value from 0 to 9999
I2 Comparison value 2 (positive value I7, I8, I11, I12, actual value T1 to T16, C1 to C16)
F2 Gain factor for I2 (I2 = F2 x actual value at I2); F2 = positive value from 0 to 9999
OS Offset for the value of I1 (I1 = OS + actual value at I1); OS = positive value from 0 to 9999
HY Switching hysteresis for value I2
Value HY applies both to positive and negative hysteresis.
I2 = Actual value at I2 + HY;
I2 = Actual value at I2 - HY;
HY= positive value from 0 to 9999
Work normally with analog inputs and setpoints as the
parameters for the analog value comparator.
easy400/600-
Parameters
easy500/700-
Parameters
AA
= I1 AA
BB
= I2 BB
A1
= A1
+
= +
> = GE
ANALOG
AAw g
n > dA1
BBy b +
A1 GE +
I1 AA Æ
F1 +0
I2 BB æ
F2 +0
OS +0
HY +0

Table of Contents