4 Wiring  with
4.10 Timing Relay
132 Operating instructions 05/10 MN05013003Z-EN www.eaton.com
4.10.5.5 Timing relay, flashing
You can set the mark to space ratio to 1:1 or 1:1.
Time value I1: mark time
Time value I2: space time
Mark-to-space ratio=1:1 flashing: S1 equals S2. Mark-to-space ratio 1:1
flashing: S1 not equal S2.
Figure 72: Timing relay signal diagram, flashing
1: trigger coil TTx
2: Stop coil HTx
3: Reset coil RTx
4: Switch contact (N/O) Tx
Range A: The relay flashes for as long as the Trigger coil is activated.
Range B: The stop coil interrupts the timing out of the set time.
Range C: The reset coil resets the relay.
4.10.6 Examples timing relay
4.10.6.1 Example: timing relay, on-delayed
In this example a conveyor belt starts 10 s after the system is powered up.
t
1
+ t
2
= t
s2
t
s1
t
s1
t
s1
t
s2
t
s2
t
s1
t
s1
t
s2
t
s2
AB
1
2
4
3
t
t
s1
t
s2
C
Circuit diagram display Parameter settings of timing relay T1
I5-------TT1
T1-------ÄQ1
T1 X S +
I1 10,000
I2