6  Internal
6.2 Delay times for inputs and outputs
190 Operating instructions 05/10 MN05013003Z-EN www.eaton.com
Figure 93: Switching behavior with input debounce disabled
Typical delay times with the debounce delay switched off are:
On delay for I1 to I12
0.25 ms (DC),
0.3 ms (easy-DA)
Off delay for
I1 to I6 and I9 to I12: 0.4 ms (easy-DC), 0.3 ms (easy-DA)
I7 and I8: 0.2 ms (DC), 0.35 ms (easy-DA)
6.2.2 Delay time with -AB, -AC basic units
The input delay with AC voltage signals depends on the frequency. The
appropriate values for 60 Hz are given in brackets:
Switch-on delay
80 ms at 50 Hz,
66 ms at 60 Hz
Off delay for
I1 to I6 and I9 to I12: 80 ms (66 ms)
I7 and I8: 160 ms (150 ms) with easy-AB
I7 and I8: 80 ms (66 ms) with easy-AC
Figure 94: On delay for easy-AC, easy-AB
Ensure clean input signals when the debounce is deactivated as
easy reacts even to very short signals.
1
0
1
0
S1
BBBBBB
A
C
I1
A
11
B
S1
t
SC2

Table of Contents