EasyManua.ls Logo

Eaton easy500, easy700

Eaton easy500, easy700
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 Wiring  with
4.5 Counter
94 Operating instructions 05/10 MN05013003Z-EN www.eaton.com
4.5 Counter
easy provides 16 up/down counters C1 to C16 for use as required. The counter
relays allow you to count events. You can define an upper threshold value as a
comparison value. The contact will switch according to the actual value.
4.5.0.1 High-speed counters, frequency counters up to 1 kHz counter frequency.
easy-DA and easy-DC feature four high-speed counters C13 to C16. The
function is defined by the mode selected. The counter input is connected
directly to a digital input. The high-speed digital inputs are I1 to I4. Possible
applications include the counting of components, lengths, events and
frequency measurement.
Table 13: Counter modes
Counters C1…C16 (Counter)
Boolean inputs/outputs Parameters
Contact Coil Input value Output value
C "1“, when actual value
setpoint value
CC Counter
input
- -
DC Count
direction
RC Reset
S setpoint value
00000 - 32000
The counters of easy500 and easy700 function in the same way
as the counters of easy400 and easy600. If required, the same
counters can be used retentively.
Counter Operating
Mode
C1 to C12 N Up/Down Counter
C13, C14
N or H Up/down counters or high-speed up counters (easy-DA, easy-DC)
C15, C16 N or F Up/down counters or frequency counters (easy-DA, easy-DC)