5 settings
5.8 Setting the cycle time
Operating instructions 05/10 MN05013003Z-EN www.eaton.com 181
5.8 Setting the cycle time
easy allows you to fix the cycle time. To do this, move to the SYSTEM menu
and from there to the CYCLE TIME… menu.
The cycle time can only be set in STOP mode.
easy is in STOP mode.
Select CYCLE-T and press OK.
The following menu appears:
Press OK.
You can now enter the set cycle time.
úí Move between the parameters.
ÍÚ Change value.
Press OK to acknowledge the value: e.g. 35 ms.
The set cycle time is at least 35 ms. The cycle time can be longer if easy
requires more time for processing the program.
Set cycle time value range:
between 00 and 60 ms.
5.9 Retention (non-volatile data storage)
Plant and machine controls require the possibility to retentively set operating
states or actual values, i.e. the values should be retained safely even after
the power supply of a machine or plant has been switched off and should be
left unchanged until the actual value is overwritten.
Default settings:
The cycle time is set to 00 ms.
P BUTTONS Æ
RUN MODE å
CARD MODE å
CYCLE-T.. æ
CYCLE TIME
00 MS
CYCLE TIME
35 MS
The entry of a set cycle time is only useful in applications
involving two-step controllers or similar functions.
With a cycle time setting of 00 ms, easy will process the circuit
diagram and the program at the fastest possible speed. (see
also inside easy… cycle time)
Default settings:
The retention function is not activated.

Table of Contents