8 Appendix
8.3 Technical data
218 Operating instructions 05/10 MN05013003Z-EN www.eaton.com
8.3.7 Relay outputs
8.3.7.1 EASY512-..-R…, EASY618-..-RE/EASY719-..-R.., EASY202-RE
EASY512-…-R… EASY618-..-RE/
EASY719-..-R..
EASY202-RE
Number 4 6 2
Type of outputs Relay
In groups of 1 1 2
Parallel switching of outputs to
increase performance
Not permissible
Protection for an output relay
Miniature circuit-breaker B16 or fuse 8 A (slow)
Potential isolation from power
supply, inputs
Yes
300 V AC (safe isolation)
600 V AC (basic isolation)
Mechanical lifespan
(Operations)
10 x 10
6
Contacts relays
Conventional therm. current 8 A (10 A UL)
Recommended for load > 500 mA, 12 V AC/DC
Protected against short-
circuit cos ϕ = 1
16 A characteristic B (B16) at 600 A
Short-circuit proof
cos ϕ = 0.5 to 0.7
16 A characteristic B (B16) at 900 A
Rated impulse withstand
voltage
Uimp
contact coil
6kV
Rated insulation voltage
Ui
Rated operational voltage
Ue
250 V AC
Safe isolation to EN 50178
between coil and contact
300 V AC
Safe isolation to EN 50178
between two contacts
300 V AC
Making capacity
AC-15 250 V AC, 3 A (600
Ops/h)
300000 operations
DC-13 L/R ≦ 150 ms 24 V DC,
1 A (500 S/h)
200000 operations
Breaking capacity
AC-15 250 V AC, 3 A (600
Ops/h)
300 000 operations
DC-13 L/R ≦ 150 ms 24 V DC,
1 A (500 S/h)