8 Appendix
8.3 Technical data
Operating instructions 05/10 MN05013003Z-EN www.eaton.com 219
8.3.7.2 UL/CSA
Filament bulb load 1000 W at 230/240 V AC/25000 operations
500 W at 115/120 V AC/25000 operations
Fluorescent tube with ballast
10 x 58 W at 230/240 V AC/25000 operations
Conventional fluorescent
tube, compensated
1 x 58 W at 230/240 V AC/25000 operations
Fluorescent tube,
uncompensated
10 x 58 W at 230/240 V AC/25000 operations
Operating frequency, relays
Mechanical switching
operations
10 million (1 x 10
7
)
Mechanical switching
frequency
10 Hz
Resistive lamp load
2 Hz
Inductive load 0.5 Hz
EASY512-…-R… EASY618-..-RE/
EASY719-..-R..
EASY202-RE
Continuous current at 240 V AC/24 V DC 10/8 A
AC Control Circuit Rating Codes
(Utilization category)
B300 Light Pilot Duty
Max. rated operational voltage
300 V AC
Max. thermal continuous current cos ϕ =1atB300 5 A
Maximum make/break capacity cos ϕ≠1 (NO/NC) at B300 3600/360 VA
DC Control Circuit Rating Codes
(Utilization category)
R300 Light Pilot Duty
Max. rated operational voltage
300 V DC
Max. thermal continuous current with R300 1 A
Maximum apparent On/off power with R300 28/28 VA