easy500/700
Standards EN 55011, EN 55022, IEC EN 61000-4, IEC60068-2-6,
IEC60068-2-27
easy200 easy512 easy600, easy700
Dimensions W x H x D
[mm] 35.5 x 90 x 56.5 71.5 x 90 x 56.5 107.5 x 90 x 56.5
[inches] 1.4 x 3.54 x 2.08 2.81 x 3.54 x 2.08 4.23 x 3.54 x 2.08
Space units (SU) width 2 SU (space units) wide 4 SU (space units) wide 6 space units wide
Weight
[g] 70 200 300
[lb] 0.154 0.441 0.661
Mounting DIN 50022, 35 mm rail or screw mounting with 3 ZB4-GF1 fixing brackets
(accessories); with easy200 only 2 fixing brackets required.
Climatic environmental conditions
(Cold to IEC 60068-2-1, Heat to IEC 60068-2-2)
Operating ambient temperature
Installed horizontally/vertically
–25 to 55 °C, –13 to 131 °F
Condensation
Prevent condensation with suitable
measures
LCD display (reliably legible)
0 - 55 °C, 32 to 131 °F
Storage/transport temperature
–40 to +70 °C, –40 to 158 °F
Relative humidity (IEC 60068-2-30)
5 to 95 %, non-condensing
Air pressure (in operation) 795 - 1080 hPa
Corrosion resistance
IEC 60068-2-42 SO
2
10 cm
3
/m
3
, 4 days
IEC 60068-2-43 H
2
S1 cm
3
/m
3
, 4 days
Inflammability class to UL 94
V 0
Ambient mechanical conditions
Pollution degree 2
Degree of protection (EN 50178, IEC 60529, VBG4)
IP20
Vibration (IEC 60068-2-6) 10 - 57 Hz (Constant amplitude 0.15 mm)
57 - 150 Hz (constant acceleration 2 g)
Shock (IEC 60068-2-27)
18 shocks (semi-sinusoidal 15 g/11 ms)
Drop (IEC 60068-2-31) Drop height 50 mm
Free fall, when packed (IEC 60068-2-32) 1 m