4 Wiring  with
4.4 Analog value comparator/threshold value switch
Operating instructions 05/10 MN05013003Z-EN www.eaton.com 85
4.4.3 Parameter display in RUN mode
Parameter display and parameter set for analog value comparator in RUN
mode with the display of the actual values:
The analog value comparator for easy500 and easy700 operates
internally in the value range:
–2147483648 to +2147483647
This ensures that the correct value is always calculated. This is
important for multiplying values (I1 x F1 or I2 x F2).
Example:
I1 = 9999, F1 = 9999
I1 x F1 = 99980001
The result is within the value range.
If no value is entered at F1 or F2, only the value at I1 and I2 is
used (no multiplication).
If the value of a control relay exceeds the value 9999, the value
of the counter is shown in the display of the analog value
comparator minus 10000.
Example: Counter actual value =10233
Display of the analog value comparator: 233 (10000 is displayed
as 0).
Actual value, e.g.: analog input
Factor is not used
Actual comparison value, e.g.: constant
Factor is not used
Offset is not used
The switching hysteresis is +/– 25
A1 EQ +
I1 0249 Æ
F1 0000
I2 0350 æ
F2 0000
OS 0000
HY 0025