4 Wiring with
4.4 Analog value comparator/threshold value switch
Operating instructions 05/10 MN05013003Z-EN www.eaton.com 85
4.4.3 Parameter display in RUN mode
Parameter display and parameter set for analog value comparator in RUN
mode with the display of the actual values:
→
The analog value comparator for easy500 and easy700 operates
internally in the value range:
–2147483648 to +2147483647
This ensures that the correct value is always calculated. This is
important for multiplying values (I1 x F1 or I2 x F2).
Example:
I1 = 9999, F1 = 9999
I1 x F1 = 99980001
The result is within the value range.
→
If no value is entered at F1 or F2, only the value at I1 and I2 is
used (no multiplication).
→
If the value of a control relay exceeds the value 9999, the value
of the counter is shown in the display of the analog value
comparator minus 10000.
Example: Counter actual value =10233
Display of the analog value comparator: 233 (10000 is displayed
as 0).
Actual value, e.g.: analog input
Factor is not used
Actual comparison value, e.g.: constant
Factor is not used
Offset is not used
The switching hysteresis is +/– 25
A1 EQ +
I1 0249 Æ
F1 0000
I2 0350 æ
F2 0000
OS 0000
HY 0025