4 Wiring with
4.10 Timing Relay
126 Operating instructions 05/10 MN05013003Z-EN www.eaton.com
For "M:S" time base
With the time base “M:S” the value is accepted as a “value in s”.
Rule:
Time setpoint = Value divided by 60 Integer result = Number of hours,
remainder is the number of minutes
For time base H:M
With the time base “H:M:” the value is accepted as a “value in M
(minutes)”.
Rule:
Time setpoint = Value divided by 60, integer result = Number of hours,
remainder is the number of minutes
Value, e.g. Analog input Time setpoint in [M:S]
0 00:00
100 01:40
300 05:00
500 08:20
1023 17:03
Value, e.g. Analog input
Time setpoint in [H:M]
0 00:00
100 01:40
300 05:00
606 10:06
1023