4 Wiring with
4.12 Year Time Switch
146 Operating instructions 05/10 MN05013003Z-EN www.eaton.com
Example 9: Selecting a time range of two days spanning the turn of the
year on 2010/2011, 2011/2012 (2-channel)
The Y1 year time switch should switch on at 00:00 on 12/31 of 2010 and
remain switched on until 00:00 on 01/02 of 2011,
and switch on at 00:00 on 12/31 of 2011 and remain switched on until 00:00
on 01/02 of 2012.
Figure 82: Select a time range of two days spanning the turn of the year
① First and ② last on year.
③ First and ④ last off year.
Example 10: Overlapping time ranges (2-channel)
This example shows how to configure the parameters for continuous
overlapping time ranges on adjacent channels.
The Y1 year time switch, channel C, switches on at 00:00 on the third of
months 5, 6, 7, 8, 9, 10 and remains switched on until 00:00 on the 26th of
these months.
The Y1 year time switch, channel D, switches on at 00:00 on the second of
months 6, 7, 8, 9, 10, 11, 12 and remains switched on until 00:00 on the 18th
of these months.
Circuit diagram display Parameter settings of the
year time switch Y1
Circuit diagram display Parameter settings of the
year time switch Y1
1/1
2010 2011
1/1
31
12
31
12
2012
Y1 A +
ON 31.12.10
OFF --.--.11
Y1 B +
ON --.--.11
OFF 12.01.01
Y1 C +
ON 03.05.--
OFF 25.10.--
Y1 D +
ON 02.06.--
OFF 17.12.--