8 Appendix
8.3 Technical data
Operating instructions 05/10 MN05013003Z-EN www.eaton.com 221
Inductive load (without external suppressor circuit)
General explanations:
T
0.95
= time in milliseconds until 95 % of the stationary current is reached.
Utilization category in groups for:
• Q1 to Q4,
• Q5 to Q8,
• S1 to S4,
• S5 to S8.
Number of outputs ≦ 4 ≦ 4
total maximum current 2.0 A, Caution! Outputs must be actuated simultaneously and for the same time
duration.
Status indication of the
outputs
LCD display (if provided)
T
0.95
≈ 3 x T
0.65
= 3 x
L
R
T
0.95
= 1 ms
R = 48 Ω
L = 16 mH
Utilization factor g = 0.25
Relative duty factor % 100
Maximum switching frequency f = 0.5
Hz
Maximum duty factor DF = 50 %
Operations/h 1500
DC13
T
0.95
= 72 ms
R = 48 Ω
L = 1.15 H
Utilization factor
g = 0.25
Relative duty factor % 100
Maximum switching frequency f = 0.5
Hz
Maximum duty factor DF = 50 %
Operations/h 1500
Other inductive loads:
T
0.95
= 15 ms
R = 48 Ω
L = 0.24 H
Utilization factor g = 0.25
Relative duty factor % 100
Maximum switching frequency f = 0.5
Hz
Maximum duty factor DF = 50 %
Operations/h 1500
Inductive load with external suppressor circuit for each load (see section “Connecting transistor outputs” on )
Utilization factor g = 1
Relative duty factor % 100
max. operating frequency
Max. duty factor
Operations/h Depending on the
suppressor circuit
EASY512-D.-T… EASY620-DC-.E, EASY72…