2 Installation
2.5 Connecting inputs
Operating instructions 05/10 MN05013003Z-EN www.eaton.com 33
2.5.1.2 Connect digital AC inputs to the expansion unit
Figure 13: Connecting EASY…-AC-E digital inputs
Table 2: easy-AB input signal values
Table 3: easy-AC input signals
Voltage range of the input signals Input current
OFF signal ON signal
easy500/
easy700
I1 - I6 0 - 6 V AC 14 - 26.4 V AC 4 mA at 24 V AC
I7, I8 7 V AC or
9.5 V DC
2 mA with 24 V AC and 24 V DC
easy700 I9, I10
14 to 26.4 V AC 4 mA at 24 V AC
I11, I12 7 V AC or
9.5 V DC
2 mA with 24 V AC and 24 V DC
Voltage range of the input signals Input current
OFF signal ON signal
easy500/
easy700
I1 - I6 0 - 40 V 79 - 264 V 0.5 mA at 230 V AC/0.25 mA at
115 V AC
I7, I8
6 mA at 230 V AC/4 mA at 115 V
easy700 I9 - I12
0.5 mA at 230 V AC/0.25 mA at
115 V AC
easy600 R1 - R12
L
N
R10R9R8R7R6R5R4R3R2R1E+ E-
R11
R12 NNL