2 Installation
2.6 Connecting outputs
Operating instructions 05/10 MN05013003Z-EN www.eaton.com 45
2.6.2.3 EASY620-..-TE
Figure 33: EASY620-…-TE transistor outputs
Parallel connection:
Up to four outputs can be connected in parallel in order to increase the
power. This enables a maximum output current of 2 A.
WARNING
The outputs may only be connected in parallel within a group
(Q1 to Q4 or Q5 to Q8, S1 to S4 or S5 to S8); Q1 and Q3 or Q5,
Q7 and Q8. Parallel outputs must be activated simultaneously.
WARNING
Please note the following when switching off inductive loads:
Suppressed inductive loads cause less interference in the
entire electrical system. It is generally recommended to
connect the suppressor as close as possible to the
inductance.
0 V H
S1 S2 S3 S4 S5 S6 S7 S8 +24 V
f 2.5 A
F10 A
0V
+ 24 V H
R
5 W/24 V
0.5 A
(20.4 – 28.8 V H)
24 V H
0.5 A
Q
Q