7 Pilot devices M22-SWD…
7.2 M22-SWD front mount
178 SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com
By changing the content of bits 5 to 7, the brightness can be reduced to any
of eight settings. The LED will continue to be switched on and off via output
Q0.
Table 48: Brightness setting
Diagnostics
In the event of a diagnosis the module reports the following error causes (0
is set for bit 4 in the input byte):
7.2.9.6 M22-SWD-K22LED-(W/B/G/R)
The function element has one input byte and one output byte at its disposal.
Input points
Byte 0:
5 DIM0 Dimming setting adjustments (device version 02 and
higher)
6
DIM1
7
DIM2
DIM2 DIM1 DIM0
0 0 0 Full brightness
0 0 1 First dimming setting
---...
1 1 1 Eighth dimming setting
Value
Description
0x10 The contact is in the middle position for longer than four
seconds.
0x11
Contact short-circuit
Bit
Designation Description
76543210
SUBST PRSNT DIAG NO2 NC2
numer-
ical
convert
er
NO1 NC1
numer-
ical
convert
er
NO2
NC2
NO1
NC1

Table of Contents