7 Pilot devices M22-SWD…
7.2 M22-SWD front mount
SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com 181
Parameterization
With the programming system’s control configurator, a user can define the
measured value refresh rate and averaging.
The specified value is the refresh time to the SmartWire-DT coordinator. An
averaging function, which smooths input signal fluctuations, is associated
with this setting.
Structure of parameter byte 0:
Value Description
0x14 Internal error
0x2B
Front element not plugged in
0x2C
Wrong front element plugged in
0x2D
Malfunctioning front element and/or plug-in connection
Parameter
Reading update Averaging
On (default) AUS
Reading refresh rate 20 ms 1 –
100 ms (default setting) 5 measurement cycles
200 ms 10 measurement cycles
500 ms 25 measurement cycles
Bit Function Configuration
0 Potentiometer data format 0 = percentage value
1 = absolute value
1
Averaging 0 = Off
1 = On
2, 3
Reading refresh rate Bit 2 Bit 3
0 0 20 ms
0 1 100 ms
1 0 200 ms
1 1 500 ms
4-7
Not used 0
Bold values indicate the default settings.
ï¿«
The CANopen field bus transmits data event-controlled when-
ever the reading changes.
Reducing the reading refresh rate, for example to 50 ms, can
increase data traffic on the field bus.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton SmartWire-DT SWD Series and is the answer not in the manual?

Eaton SmartWire-DT SWD Series Specifications

General IconGeneral
BrandEaton
ModelSmartWire-DT SWD Series
CategoryControl Unit
LanguageEnglish

Related product manuals