7 Pilot devices M22-SWD…
7.2 M22-SWD front mount
184 SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com
Reset value as an unsigned integer
The reset value can be set either by the PLC with a rising edge on output
byte 0, bit 1 or with the confirmation button (parameter byte 0, bit 6 must be
set to 1), table 50. If the reset value is invalid (e.g., falls outside the set
limits), the value will not be applied and the existing value will be retained.
If the reset value needs to be changed, a reset must first be performed once
by the PLC for confirmation purposes. This will cause the new reset value to
be applied, after which the new reset value can be set with the confirmation
button as well. If the PLC has not set a valid reset value by this point, the
value will be set to the lower limit when the confirmation button is pressed
(parameter byte 0, bit 6 must be set to 1), provided the limits are activated;
otherwise, it will be set to 0, table 50.
Profile 2
Byte 0:
The reset value can be set either by the PLC with a rising edge on output
byte 0, bit 1 or with the confirmation button (parameter byte 0, bit 6 must be
set to 1), table 51. The reset value can be changed by changing the value
of bytes 5 and 6 in parameter byte 0.
Address Byte 1 Byte 0
Bit
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
QW1
MSB
LSB
76543210
––––––RESETACK
CTRC
Bit
Designation Description
0 ACKCTRC The confirmation button's acknowledge signal is triggered with
a rising edge
1
RESET The counter value is reset to the value defined in parameter
bytes 5 and 6 with a rising edge, Unbekannte Quelle des
Querverweises
2
Not used
3
Not used
4
Not used
5
Not used
6
Not used
7
Not used