11 Interface for NZM compact circuit-breakers
11.8 Programming
SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com 235
11.8.1.2 Special considerations when using the module with a CANopen field bus
When using data profile 1, 3 or 4 in conjunction with SmartWire gateway
EU5C-SWD-CAN, entries in the setting range for associated service data
objects (SDO) 2102subx must be changed in the PLC configuration program.
With programming system CoDeSys, for example, change the default value
from 0xA2D392 to 0xA2D592 to use PKE profile 3.
In programming systems with a controller configurator without automatic
profile selection for SDO parameterization the corresponding SDO object
2102subx is inserted in the SDO object list and its content transferred when
data profile 1, 3 or 4 is used.
Byte Profile 1 Profile 2 (default) Profile 3 Profile 4
0 SWD status byte SWD status byte SWD status byte SWD status byte
1
Status byte 0 LVSG Status byte 0 LVSG Status byte 0 LVSG Status byte 0 LVSG
2
Status byte 1 LVSG Status byte 1 LVSG Status byte 1 LVSG Status byte 1 LVSG
3/4
Current I1 Current I1 Current I1
5/6
Current I2 Current I2 Current I2
7/8
Current I3 Current I3 Current I3
9/10
Current Imax Current I
max
Current I
max
11 S0 value high
section
S0 value high section
12
S0 value high
section
S0 value high section
13
S0 value low section S0 value low section
14
S0 value low section S0 value low section
15
Set value LS for I
r
16 Set value I
i
17 Set value t
r
18 Set value I
sd
19 Set value t
sd
20 Set value I
g
21 Set value t
g
22 I²t of the CB on/off
23
Serial number NZM
H byte
24
Serial number NZM
M byte
25
Serial number NZM
L byte
26
CB part no.
27
LS function
28
NZM version
29
Earth fault module
30
Free