iTEMP TMT162 Technische Daten
Endress+Hauser 55
Designation Standard
Ambient temperature:
Influence (±) per 1 °C (1.8 °F) change
Supply voltage:
Influence (±) per V change
Ni100 (6)
DIN 43760
IPTS-68
≤ 0.004 °C
(0.007 °F)
-
≤ 0.005 °C
(0.009 °F)
-
Ni120 (7) - -
Cu50 (10)
OIML R84:
2003 /
GOST
6651-2009
≤ 0.007
°C
(0.013 °F)
-
≤ 0.008 °C
(0.014 °F)
-
Cu100 (11)
0.002% * (MV - LRV),
at least 0.004 °C (0.007 °F)
≤ 0.004 °C
(0.007 °F)
0.002% * (MV - LRV),
at least 0.004 °C (0.007 °F)
Ni100 (12)
≤ 0.004 °C
(0.007 °F)
- -
Ni120 (13) - -
Cu50 (14)
OIML R84:
2003 /
GOST 6651-94
≤ 0.007 °C
(0.013 °F)
-
≤ 0.008 °C
(0.014 °F)
-
Resistance transmitter (Ω)
10 to 400 Ω ≤ 6 mΩ
0.0015% * (MV - LRV),
at least 1.5 mΩ
0.001 %
≤ 6 mΩ
0.0015% * (MV - LRV),
at least 1.5 mΩ
0.001 %
10 to 2000
≤ 30 mΩ 0.0015% * (MV - LRV),
at least 15 mΩ
≤ 30 mΩ 0.0015% * (MV - LRV),
at least 15 mΩ
1)
Measured value transmitted via HART
®
.
2) Percentages based on the configured span of the analog output signal
Influence of ambient temperature and supply voltage on operation for thermocouples (TC) and voltage transmitters
Designation Standard
Ambient temperature:
Influence (±) per 1 °C (1.8 °F) change
Supply voltage:
Influence (±) per V change
Digital
1)
D/A
2)
Digital D/A
Maximum Based on measured value Maximum Based on measured value
Type A (30)
IEC 60584-1
0.13 °C
(0.23 °F)
0.0055% * (MV - LRV),
at least 0.03 °C (0.054 °F)
0.001 %
≤ 0.07 °C
(0.13 °F)
0.0054% * (MV - LRV),
at least 0.02 °C (0.036 °F)
0.001 %
Type B (31)
≤ 0.06 °C
(0.11 °F)
-
≤ 0.06 °C
(0.11 °F)
-
Type C (32)
IEC 60584-1 /
ASTM E988-96
≤ 0.08 °C
(0.14 °F)
0.0045% * (MV - LRV),
at least 0.03 °C (0.054 °F)
≤ 0.04 °C
(0.07 °F)
0.0045% * (MV - LRV),
at least 0.03 °C (0.054 °F)
Type D (33) ASTM E988-96
0.004% * (MV - LRV),
at least 0.035 °C (0.063 °F)
0.004% * (MV - LRV),
at least 0.035 °C (0.063 °F)
Type E (34)
IEC 60584-1
≤ 0.03 °C
(0.05 °F)
0.003% * (MV - LRV),
at least 0.016 °C (0.029 °F)
≤ 0.02 °C
(0.04 °F)
0.003% * (MV - LRV),
at least 0.016 °C (0.029 °F)
Type J (35)
≤ 0.04 °C
(0.07 °F)
0.0028% * (MV - LRV),
at least 0.02 °C (0.036 °F)
0.0028% * (MV - LRV),
at least 0.02 °C (0.036 °F)
Type K (36)
0.003% * (MV - LRV),
at least 0.013 °C (0.023 °F)
0.003% * (MV - LRV),
at least 0.013 °C (0.023 °F)
Type N (37)
0.0028% * (MV - LRV),
at least 0.020 °C (0.036 °F)
0.0028% * (MV - LRV),
at least 0.020 °C (0.036 °F)
Type R (38)
≤ 0.05 °C
(0.09 °F)
0.0035% * (MV - LRV),
at least 0.047 °C (0.085 °F)
≤ 0.05 °C
(0.09 °F)
0.0035% * (MV - LRV),
at least 0.047 °C (0.085 °F)
Type S (39) - -
Type T (40)
≤ 0.01 °C
(0.02 °F)
-
≤ 0.01 °C
(0.02 °F)
-
Type L (41)
DIN 43710
≤ 0.02 °C
(0.04 °F)
- -
Type U (42)
≤ 0.01 °C
(0.02 °F)
- -