3 Transducer Blocks (transmission blocks) PROline Prosonic Flow 93 FOUNDATION Fieldbus
118 Endress+Hauser
Pipe Data -
Sound Velocity
Pipe
AUTO - OOS Entry of the sound velocity in the pipe.
Measuring the sound velocity in the pipe
Measurement can be carried out via:
• The local display (“Sensor” Quick Setup), see Page 19.
• The configuration and service software FieldTool.
Note!
A reference value is used as a basis for measuring the sound
velocity. This reference value can be edited, (see Page 117).
User input:
Fixed-point number 800...6500 (m/s)
Factory setting:
3120 (m/s)
Note!
The unit used is displayed in the “Pipe Data - Unit Sound Velocity
Pipe” parameter.
Pipe Data -
Unit Sound
Velocity Pipe
read only Displays the unit for the sound velocity in the pipe.
Note!
The unit is selected in the “System Unit - Sound Velocity”
parameter, see Page 111.
Pipe Data -
Circumference
AUTO - OOS Entry of the pipe circumference.
User input:
Fixed-point number 31.4...15708.0 (mm)
Factory setting:
279.3 (mm)
Note!
The unit used is displayed in the “Pipe Data - Unit Circumference”
parameter.
Pipe Data -
Unit
Circumference
read only Displays the unit for the pipe circumference.
Note!
The unit is selected in the “System Unit - Length” parameter, see
Page 112.
Pipe Data -
Pipe Diameter
AUTO - OOS Entry of the pipe diameter.
User input:
Fixed-point number 10.0...5000.0 (mm)
Factory setting:
88.9 (mm)
Note!
The unit used is displayed in the “Pipe Data - Unit Pipe Diameter”
parameter.
“TRANSDUCER_CH1” and “TRANSDUCER_CH2” (E+H parameters) /
Base index 1200 and 1300
Parameter Write access
with operating
mode
(MODE_BLK)
Description