Diagnosis and troubleshooting Proline Prosonic Flow P 500 HART
162 Endress+Hauser
12.2 Diagnostic information via LEDs
12.2.1 Transmitter
Proline 500
Different LEDs in the transmitter provide information on the device status.
A0029629
1 Supply voltage
2 Device status
3 Not used
4 Communication
5 Service interface (CDI) active
LED Color Meaning
1 Supply voltage Off Supply voltage is off or too low.
Green Supply voltage is ok.
2 Device status (normal
operation)
Off Firmware error
Green Device status is ok.
Flashing green Device is not configured.
Red A diagnostic event with "Alarm" diagnostic behavior
has occurred.
Flashing red A diagnostic event with "Warning" diagnostic
behavior has occurred.
Flashing red/green The device restarts.
2 Device status (during
start-up)
Flashes red slowly If > 30 seconds: problem with the boot loader.
Flashes red quickly If > 30 seconds: compatibility problem when
reading the firmware.
3 Not used – –
4 Communication Off Communication not active.
White Communication active.
5 Service interface (CDI) Off Not connected or no connection established.
Yellow Connected and connection established.
Flashing yellow Service interface active.