Proline Prosonic Flow P 500 HART Commissioning
Endress+Hauser 103
Parameter Prerequisite Description Selection / User
entry / User
interface
Factory setting
Intermediate pipe length The 1 measuring point - 2
signal paths option is selected
in Measuring point
configuration parameter.
Enter the length of the
intermediate pipe between the
two bends.
Positive floating-
point number
0 mm
Inlet diameter The 1 measuring point - 2
signal paths option is
selected in the Measuring
point configuration
parameter.
The Concentric diameter
change option is selected in
the Inlet configuration
parameter.
Enter the outer diameter of the
pipe before the cross-section
change. For convenience, the
same measuring pipe wall
thickness as for the clamp-on
system is applied.
1 to 10 000 mm 88.9 mm
Transition length In the Measuring point
configuration parameter,
the 1 measuring point - 2
signal paths option is
selected.
In the Inlet configuration
parameter, the Concentric
diameter change option is
selected.
Enter length of the concentric
diameter change.
0 to 20 000 mm 0 mm
Inlet run The 1 measuring point - 2
signal paths option is selected
in Measuring point
configuration parameter.
Enter length of the available
straight inlet run.
0 to 300 000 mm 0 mm
Relative sensor position The 1 measuring point - 2
signal paths option is selected
in the Measuring point
configuration parameter and
the Off option is not selected
in FlowDC inlet configuration
parameter.
Shows the correct position for
the sensor.
90°
180°
Result sensor type / mounting type Shows the selected sensor type
and (if applicable
automatically) selected
mounting type.
e.g. C-100-A option /
(2) V-mounting
option
Result sensor distance / measuring
aid
Shows the calculated sensor
distance and vernier or wire
length (if applicable) required
for installation.
e.g. 201.3 mm / B 21
* Visibility depends on order options or device settings
10.4.4 Checking the installation status
The status of individual parameters can be checked in the Installation status submenu.
Navigation
"Setup" menu → Installation status
Installation status
Installation status (2958)
→  104
Signal strength (2914)
→  104