Proline Prosonic Flow P 500 HART Electrical connection
Endress+Hauser 47
Pulse output, phase-shifted
Standard installation cable is sufficient.
Relay output
Standard installation cable is sufficient.
Current input 0/4 to 20 mA
Standard installation cable is sufficient
Status input
Standard installation cable is sufficient
Cable diameter
• Cable glands supplied:
M20 × 1.5 with cable ⌀ 6 to 12 mm (0.24 to 0.47 in)
• Spring-loaded terminals: Suitable for strands and strands with ferrules.
Conductor cross-section 0.2 to 2.5 mm
2
(24 to 12 AWG).
Connecting cable between the transmitter and sensor
Sensor cable for sensor - transmitter: Proline 500
Standard cable • TPE: -40 to +80 °C (-40 to +176 °F)
• TPE armored: -40 to +80 °C (-40 to +176 °F)
• TPE halogen-free: -40 to +80 °C (-40 to +176 °F)
• PTFE: -50 to +170 °C (-58 to +338 °F)
• PTFE armored: -50 to +170 °C (-58 to +338 °F)
Cable length (max.) 30 m (90 ft)
Cable lengths (available for
order)
5 m (15 ft), 10 m (30 ft), 15 m (45 ft), 30 m (90 ft)
Operating temperature Depends on the device version and how the cable is installed:
Standard version:
• Cable - fixed installation
1)
: minimum –40 °C (–40 °F) or –50 °C (–58 °F)
• Cable - movable installation: minimum –25 °C (–13 °F)
1) Compare details under the row "Standard cable"
7.2.3 Terminal assignment
Transmitter: supply voltage, input/outputs
The terminal assignment of the inputs and outputs depends on the individual order
version of the device. The device-specific terminal assignment is documented on an
adhesive label in the terminal cover.
Supply voltage Input/output
1
Input/output
2
Input/output
3
1 (+) 2 (–) 26 (+) 27 (–) 24 (+) 25 (–) 22 (+) 23 (–)
Device-specific terminal assignment: adhesive label in terminal cover.
Transmitter and sensor connection housing: connecting cable
The sensor and transmitter, which are mounted in separate locations, are interconnected
by a connecting cable. The cable is connected via the sensor connection housing and the
transmitter housing.