12.6 Adapting the diagnostic information
12.6.1 Adapting the diagnostic behavior
Each item of diagnostic information is assigned a specific diagnostic behavior at the
factory. The user can change this assignment for specific diagnostic information in the
Diagnostic behavior submenu.
Expert → System → Diagnostic handling → Diagnostic behavior
Event no. 044
/ ../Event level
Event no. 801
Event no. 274
Warning
A0014048-EN
70 Using the example of the local display
You can assign the following options to the diagnostic number as the diagnostic behavior:
Options Description
Alarm The device stops measurement. The signal outputs and totalizers assume the defined
alarm condition. A diagnostic message is generated.
The background lighting changes to red.
Warning The device continues to measure. The signal outputs and totalizers are not affected. A
diagnostic message is generated.
Logbook entry only The device continues to measure. The diagnostic message is only displayed in the Event
logbook submenu (Event list submenu) and is not displayed in alternating sequence
with the operational display.
Off The diagnostic event is ignored, and no diagnostic message is generated or entered.
12.6.2 Adapting the status signal
Each item of diagnostic information is assigned a specific status signal at the factory. The
user can change this assignment for specific diagnostic information in the Diagnostic
event category submenu.
Expert → Communication → Diagnostic event category
Available status signals
Configuration as per HART 7 Specification (Condensed Status), in accordance with
NAMUR NE107.
Symbol Meaning
A0013956
Failure
A device error has occurred. The measured value is no longer valid.
A0013959
Function check
The device is in service mode (e.g. during a simulation).
A0013958
Out of specification
The device is being operated:
• Outside its technical specification limits (e.g. outside the process temperature range)
• Outside of the configuration carried out by the user (e.g. maximum flow in parameter
20 mA value)