1. Depending on the device version: Loosen the securing clamp of the connection
compartment cover.
2. Unscrew the connection compartment cover.
3. Turn the display module to the desired position: max. 8 × 45° in each direction.
4. Screw on the connection compartment cover.
5. Depending on the device version: Attach the securing clamp of the connection
compartment cover.
6.3 Post-mounting check
Is the measuring device undamaged (visual inspection)?
Does the measuring device correspond to the measuring point specifications?
For example:
Process temperature →  206
Inlet run conditions
Ambient temperature
Measuring range
Has the correct orientation for the sensor been selected →  19?
According to sensor type
According to medium temperature
According to medium properties (outgassing, with entrained solids)
Are the sensors correctly connected to the transmitter (upstream/downstream) ?
Are the sensors correctly mounted (distance, 1 traverse, 2 traverses) →  22?
Is the tag name and labeling correct (visual inspection)?
Is the device sufficiently protected from precipitation and direct sunlight?
Are the securing screw and securing clamp tightened securely?
Is the sensor holder properly grounded (in the event of different potential between the sensor
holder and transmitter)?