Proline Prosonic Flow P 500 HART Commissioning
Endress+Hauser 117
Parameter Prerequisite Description Selection / User
interface / User
entry
Factory setting
Switch-off value • The Switch option is
selected in the Operating
mode parameter.
• The Limit option is selected
in the Switch output
function parameter.
Enter limit value for switch-off
point (process variable <
switch-off value = open,
nonconductive).
Signed floating-point
number
Depends on country
Switch-on delay • The Switch option is
selected in the Operating
mode parameter.
• The Limit option is selected
in the Switch output
function parameter.
Enter a delay before the output
is switched on.
0.0 to 100.0 s 0.0 s
Switch-off delay • The Switch option is
selected in the Operating
mode parameter.
• The Limit option is selected
in the Switch output
function parameter.
Enter a delay before the output
is switched off.
0.0 to 100.0 s 0.0 s
Failure mode – Select output behavior in the
event of a device alarm.
• Actual status
• Open
• Closed
Open
Invert output signal – Invert the output signal. • No
• Yes
No
* Visibility depends on order options or device settings
10.4.10 Configuring the relay output
The Relay output wizard guides the user systematically through all the parameters that
have to be set for configuring the relay output.
Navigation
"Setup" menu → Relay output 1 to n
‣
Relay output 1 to n
Terminal number
→ 118
Relay output function
→ 118
Assign flow direction check
→ 118
Assign limit
→ 118
Assign diagnostic behavior
→ 118
Assign status
→ 119
Switch-off value
→ 119
Switch-off delay
→ 119