Proline Prosonic Flow P 500 HART Commissioning
Endress+Hauser 107
Failure mode
→ 107
Failure value
→ 107
Parameter overview with brief description
Parameter Prerequisite Description User interface /
Selection / User
entry
Factory setting
Terminal number – Shows the terminal numbers
used by the current input
module.
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
–
Signal mode – Select the signal mode for the
current input.
• Passive
• Active
*
Passive
0/4 mA value – Enter 4 mA value. Signed floating-point
number
0
20 mA value – Enter 20 mA value. Signed floating-point
number
Depends on country
and nominal
diameter
Current span – Select current range for
process value output and
upper/lower level for alarm
signal.
• 4...20 mA (4...20.5
mA)
• 4...20 mA NE
(3.8...20.5 mA)
• 4...20 mA US
(3.9...20.8 mA)
• 0...20 mA (0...20.5
mA)
Country-specific:
• 4...20 mA NE
(3.8...20.5 mA)
• 4...20 mA US
(3.9...20.8 mA)
Failure mode – Define input behavior in alarm
condition.
• Alarm
• Last valid value
• Defined value
Alarm
Failure value In the Failure mode
parameter, the Defined value
option is selected.
Enter value to be used by the
device if input value from
external device is missing.
Signed floating-point
number
0
* Visibility depends on order options or device settings
10.4.8 Configuring the current output
The Current output wizard guides you systematically through all the parameters that have
to be set for configuring the current output.
Navigation
"Setup" menu → Current output
‣
Current output 1 to n
Terminal number
→ 108
Signal mode
→ 108
Process variable current output
→ 108
Current range output
→ 108