Proline Prosonic Flow P 500 HART Electrical connection
Endress+Hauser 55
7.4 Potential equalization
7.4.1 Requirements
For potential equalization:
Pay attention to in-house grounding concepts
Take account of operating conditions like the pipe material and grounding
Medium, Connect the sensor and transmitter to the same electric potential
4)
Use a ground cable with a minimum cross-section of 6 mm
2
(10 AWG) and a cable lug
for potential equalization connections
7.5 Special connection instructions
7.5.1 Connection examples
Current output 4 to 20 mA HART
4
4...20 mA
5
2
1
3
6
A0029055
 46 Connection example for 4 to 20 mA HART current output (active)
1 Automation system with current input (e.g. PLC)
2 Ground cable shield at one end. The cable shield must be grounded at both ends to comply with EMC
requirements; observe cable specifications →  202
3 Connection for HART operating devices →  82
4 Resistor for HART communication (≥ 250 Ω): observe maximum load →  196
5 Analog display unit: observe maximum load →  196
6 Transmitter
2
3
4...20 mA
41
5
A0028762
 47 Connection example for 4 to 20 mA HART current output (passive)
1 Automation system with current input (e.g. PLC)
2 Power supply
3 Ground cable shield at one end. The cable shield must be grounded at both ends to comply with EMC
requirements; observe cable specifications
4 Analog display unit: observe maximum load →  196
5 Transmitter
4)