Proline Prosonic Flow P 500 HART Commissioning
Endress+Hauser 115
Configuring the switch output
Navigation
"Setup" menu → Pulse/frequency/switch output
Pulse/frequency/switch output
1 to n
Operating mode
→  115
Terminal number
→  115
Signal mode
→  115
Switch output function
→  116
Assign diagnostic behavior
→  116
Assign limit
→  116
Assign flow direction check
→  116
Assign status
→  116
Switch-on value
→  116
Switch-off value
→  117
Switch-on delay
→  117
Switch-off delay
→  117
Failure mode
→  117
Invert output signal
→  117
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
interface / User
entry
Factory setting
Operating mode Define the output as a pulse,
frequency or switch output.
Pulse
Frequency
Switch
Pulse
Terminal number Shows the terminal numbers
used by the PFS output
module.
Not used
24-25 (I/O 2)
22-23 (I/O 3)
Signal mode Select the signal mode for the
PFS output.
Passive
Active
*
Passive NE
Passive