Mounting Proline Prosonic Flow P 500 HART
22 Endress+Hauser
B
A
C
D D
C
C
D D
C
A0041975
 8 Two-path measurement: examples of the horizontal arrangement of the sensor sets at a measuring point
A Installation of the sensor sets for measurement via 1 traverse
B Installation of the sensor sets for measurement via 2 traverses
C For horizontal orientation: non-recommended installation range (60°)
D For horizontal orientation: recommended installation range max. 120°
If extending the measuring point from single-path measurement to two-path
measurement, a sensor of the same design must be selected.
Dimensions
For the dimensions and installation lengths of the device, see the "Technical
Information" document, "Mechanical construction" section .
6.1.2 Sensor set selection and arrangement
If mounting horizontally, always mount the sensor set so that it is offset at an angle
of ±30° to the top of the measuring pipe to avoid incorrect measurements caused by
gas pockets or bubbles at the top of the pipe.