Proline Prosonic Flow P 500 HART Mounting
Endress+Hauser 21
1
10 × DN
3× DN
4
a
b
C
A
B
D
6
5
15 × DN
15 × DN
20 × DN
20 × DN
3
0…15 × DN
0…15 × DN
2
15 × DN
A0053303
7
A Inlet and outlet runs DN 50 to 4000 (2 to 160")
B Inlet and outlet runs DN 15 to 65 (½ to 2½")
C Inlet and outlet runs for high-temperature sensors
D Position of inlet and outlet runs on sensor
1 Pipe elbow 90° or 45°
2 Two pipe elbows 90° or 45° (in one plane, with 0 to 15 x DN between the elbows)
3 Two pipe elbows 90° or 45° (in two planes, with 0 to 15 x DN between the elbows)
4a Reduction
4b Extension
5 Control valve (2/3 open)
6 Pump
Measuring mode
Two-path measurement with FlowDC
1)
(standard configuration)
In the case of two-path measurement with FlowDC, the flow is measured by two
measurements at the measuring point.
For this, the two sensor sets are installed on the measuring pipe, offset at a specific angle
to one another (180° for 1 traverse, 90° for 2 traverses, angle tolerance ±5°). This
arrangement is independent of the circumferential position of the two sensor sets on the
measuring pipe.
The measured values of both sensor sets are averaged. The resulting measurement error is
compensated based on the type of interference, the distance from the measuring point to
the disturbance point, and the Reynolds number. The error-compensated average thus
ensures that the specified maximum measurement error and repeatability are maintained
even under non-ideal flow conditions (see for example → 6, 20).
The configuration of the two measuring paths is only performed once and is adopted for
both measuring paths.
1) Flow disturbance compensation