Proline Prosonic Flow P 500 HART Operation
Endress+Hauser 155
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry / User
interface
Factory setting
Control Totalizer 1 to n A process variable is selected
in the Assign process variable
parameter (→ 128) of the
Totalizer 1 to n submenu.
Control totalizer value. • Totalize
• Reset + hold
• Preset + hold
• Reset + totalize
• Preset + totalize
• Hold
Totalize
Preset value 1 to n A process variable is selected
in the Assign process variable
parameter (→ 128) of the
Totalizer 1 to n submenu.
Specify start value for totalizer.
Dependency
The unit of the selected
process variable is
defined in the Unit
totalizer parameter
(→ 129) for the
totalizer.
Signed floating-point
number
Depends on country:
• 0 m³
• 0 ft³
Totalizer value One of the following options is
selected in the Assign process
variable parameter
(→ 128) of the Totalizer
1 to n submenu:
• Volume flow
• Mass flow
Displays the current totalizer
counter value.
Signed floating-point
number
–
Reset all totalizers – Reset all totalizers to 0 and
start.
• Cancel
• Reset + totalize
Cancel
11.6.1 Function scope of "Control Totalizer" parameter
Options Description
Totalize The totalizer is started or continues running.
Reset + hold The totaling process is stopped and the totalizer is reset to 0.
Preset + hold
1)
The totaling process is stopped and the totalizer is set to its defined start value
from the Preset value parameter.
Reset + totalize The totalizer is reset to 0 and the totaling process is restarted.
Preset + totalize
1)
The totalizer is set to the defined start value in the Preset value parameter and the
totaling process is restarted.
Hold Totalizing is stopped.
1) Visible depending on the order options or device settings
11.6.2 Function range of "Reset all totalizers" parameter
Options Description
Cancel No action is executed and the user exits the parameter.
Reset + totalize Resets all totalizers to 0 and restarts the totaling process. This deletes all the
previously aggregated flow values.