Commissioning Proline Prosonic Flow P 500 HART
116 Endress+Hauser
Parameter Prerequisite Description Selection / User
interface / User
entry
Factory setting
Switch output function The Switch option is selected
in the Operating mode
parameter.
Select function for switch
output.
Off
On
Diagnostic
behavior
Limit
Flow direction
check
Status
Off
Assign diagnostic behavior In the Operating mode
parameter, the Switch
option is selected.
In the Switch output
function parameter, the
Diagnostic behavior option
is selected.
The output is switched on
(closed, conductive), if there is
a pending diagnostic event of
the assigned behavioral
category.
Alarm
Alarm or warning
Warning
Alarm
Assign limit The Switch option is
selected in the Operating
mode parameter.
The Limit option is selected
in the Switch output
function parameter.
Select the variable to monitor
in case the specified limit value
is exceeded. If a limit value is
exceeded, the output is
switched on (conductive).
Off
Volume flow
Mass flow
Flow velocity
Sound velocity
Temperature
*
Pressure
*
Density
*
Reference density
*
S&W volume flow
*
GSV flow
*
NSV flow
*
API gravity
*
API slope
*
Signal strength
*
Signal to noise
ratio
*
Acceptance rate
*
Turbulence
*
Electronics
temperature
Totalizer 1
Totalizer 2
Totalizer 3
Profile factor
*
Cross flow factor
*
Volume flow
Assign flow direction check The Switch option is
selected in the Operating
mode parameter.
The Flow direction check
option is selected in the
Switch output function
parameter.
Select process variable for flow
direction monitoring.
Off
Volume flow
Mass flow
Flow velocity
Volume flow
Assign status The Switch option is
selected in the Operating
mode parameter.
The Status option is
selected in the Switch
output function parameter.
Select the device function for
which to report the status. If
the function is triggered, the
output is closed and conductive
(standard configuration).
Off
Low flow cut off
Product
identification
*
Low flow cut off
Switch-on value The Switch option is
selected in the Operating
mode parameter.
The Limit option is selected
in the Switch output
function parameter.
Enter limit value for switch-on
point (process variable >
switch-on value = closed,
conductive).
Signed floating-point
number
Depends on country