Commissioning Proline Prosonic Flow P 500 HART
108 Endress+Hauser
Lower range value output
→  109
Upper range value output
→  109
Fixed current
→  109
Damping current output
→  109
Failure behavior current output
→  109
Failure current
→  109
Parameter overview with brief description
Parameter Prerequisite Description User interface / 
Selection / User
entry
Factory setting
Terminal number Shows the terminal numbers
used by the current output
module.
Not used
26-27 (I/O 1)
24-25 (I/O 2)
22-23 (I/O 3)
Signal mode Select the signal mode for the
current output.
Active
*
Passive
*
Active
Process variable current output Select the process variable for
the current output.
Off
*
Volume flow
Mass flow
Flow velocity
Sound velocity
Temperature
*
Pressure
*
Density
*
Reference density
*
S&W volume flow
*
GSV flow
*
NSV flow
*
API gravity
*
API slope
*
Signal strength
*
Signal to noise
ratio
*
Acceptance rate
*
Turbulence
*
Electronics
temperature
Profile factor
*
Cross flow factor
*
Volume flow
Current range output Select current range for
process value output and
upper/lower level for alarm
signal.
4...20 mA NE
(3.8...20.5 mA)
4...20 mA US
(3.9...20.8 mA)
4...20 mA (4...20.5
mA)
0...20 mA (0...20.5
mA)
Fixed value
Depends on country:
4...20 mA NE
(3.8...20.5 mA)
4...20 mA US
(3.9...20.8 mA)