Commissioning Proline Prosonic Flow P 500 HART
108 Endress+Hauser
Lower range value output
→ 109
Upper range value output
→ 109
Fixed current
→ 109
Damping current output
→ 109
Failure behavior current output
→ 109
Failure current
→ 109
Parameter overview with brief description
Parameter Prerequisite Description User interface /
Selection / User
entry
Factory setting
Terminal number – Shows the terminal numbers
used by the current output
module.
• Not used
• 26-27 (I/O 1)
• 24-25 (I/O 2)
• 22-23 (I/O 3)
–
Signal mode – Select the signal mode for the
current output.
• Active
*
• Passive
*
Active
Process variable current output – Select the process variable for
the current output.
• Off
*
• Volume flow
• Mass flow
• Flow velocity
• Sound velocity
• Temperature
*
• Pressure
*
• Density
*
• Reference density
*
• S&W volume flow
*
• GSV flow
*
• NSV flow
*
• API gravity
*
• API slope
*
• Signal strength
*
• Signal to noise
ratio
*
• Acceptance rate
*
• Turbulence
*
• Electronics
temperature
• Profile factor
*
• Cross flow factor
*
Volume flow
Current range output – Select current range for
process value output and
upper/lower level for alarm
signal.
• 4...20 mA NE
(3.8...20.5 mA)
• 4...20 mA US
(3.9...20.8 mA)
• 4...20 mA (4...20.5
mA)
• 0...20 mA (0...20.5
mA)
• Fixed value
Depends on country:
• 4...20 mA NE
(3.8...20.5 mA)
• 4...20 mA US
(3.9...20.8 mA)