EasyManua.ls Logo

Endress+Hauser Proline Prosonic Flow P 500 - Page 102

Endress+Hauser Proline Prosonic Flow P 500
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning Proline Prosonic Flow P 500 HART
102 Endress+Hauser
Parameter Prerequisite Description Selection / User
entry / User
interface
Factory setting
Pipe wall thickness Enter the pipe wall thickness. Positive floating
point number
3 mm
Liner material Select liner material. None
Cement
Rubber
Epoxy resin
Unknown liner
material
None
Liner sound velocity The Unknown liner material
option is selected in the Liner
material parameter.
Define the sound velocity of
liner material.
800.0 to 3 800.0 m/s 2 400.0 m/s
Liner thickness Define the thickness of liner. 0 to 100 mm 0 mm
Sensor type Select sensor type. C-030-A
C-050-A
C-100-A
C-100-B
C-100-C
C-200-A
C-200-B
C-200-C
C-500-A
CH-050-A
*
CH-100-A
*
As per order
Sensor coupling The following option is
selected in Sensor type
parameter:
C-030-A
C-050-A
C-100-A
C-100-B
C-100-C
C-200-A
C-200-B
C-200-C
C-500-A
Select coupling medium. Coupling pad
Coupling paste
Coupling pad
Mounting type Select how the sensors are
arranged to each other.
(1) direct option: sensor
arrangement with 1 traverse
(2) V-mounting option:
sensor arrangement with 2
traverses
(3) Z-Mounting option:
sensor arrangement with 3
traverses
(4) W-mounting option:
sensor arrangement with 4
traverses
(1) direct
(2) V-mounting
(3) Z-Mounting
(4) W-mounting
Automatic
Automatic
Cable length Enter length of sensor cables. 0 to 200 000 mm As per order
FlowDC inlet configuration The 1 measuring point - 2
signal paths option is selected
in the Measuring point
configuration parameter.
Select FlowDC inlet
configuration.
Off
Single elbow
Double elbow
Double elbow 3D
45° bend
2 x 45° bend
Concentric
diameter change
Other
*
Off