EasyManua.ls Logo

Endress+Hauser Prosonic S FMU90 - HART Address; HART Settings Submenu (Only for Current Output 1)

Endress+Hauser Prosonic S FMU90
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The "output/calculations" menu (for HART instruments)
130
6.3 "HART settings" submenu
(only for current output 1)
6.3.1 "HART settings"
"HART address"
Defines the communication address for the instrument.
Range of values:
for standard operation: 0 (default)
for multidrop operation: 1 - 15
!
Note!
In multidrop operation, the ouptput current is 4 mA by default. However, it can be adjusted in the
"mA value" parameter of the "mode current" parameter set (see above).
"no. of preambles"
Specifies the number of preambles for the HART protocol. For lines with communication problems
a slight increase of this value is recommended.
"short TAG HART"
in preparation
HART settings O1203
HART address:
no. of preambles:
short TAG HART:

Table of Contents

Other manuals for Endress+Hauser Prosonic S FMU90

Related product manuals