The "level" menu
22
2.1.4 "LVL N full calibration" (N = 1 or 2)
"full F"
"blocking distance"
Indicates the blocking distance of the respective sensor. The blocking distance is measured from the
sensor membrane.
⇒
LVL1 full calib. L1006
full F: 0,00 m
block.dist. BD:
L00-FMU90xxx-19-00-00-yy-008
Use this parameter to specify the span F, i.e. the distance from the
minimum level to the maximum level.
– Default setting: depending on sensor type
– Range of values: depending on sensor type
– blocking distance BD: depending on sensor type (see table)
"
Caution!
The maximum level may not project into the blocking distance:
F
max
= E - BD
20 mA
100%
0/4 mA
0%
BD
F
E
Type of sensor blocking distance (BD) maximum measuring
distance
1)
1) valid for optimum process conditions
FDU91/FDU91F 0,3 m 10 m (for liquids)
FDU92 0,4 m 20 m (for liquids)
FDU93 0,6 m 25 m (for liquids)
FDU95 - *1*** (low temperature version) 0,7 m 45 m (for solids)
FDU95 - *2*** (high temperature version) 0,9 m 45 m (for solids)
FDU96 1,6 m 70 m (for solids)
FDU80/FDU80F 0,3 m 5 m (for liquids)
FDU81/81F 0,5 m 10 m (for liquids)
FDU82 0,8 m 20 m (for liquids)
FDU83 1 m 25 m (for liquids)
FDU84 0,8 m 25 m (for solids)
FDU85 0,8 m 45 m (for solids)
FDU86 1,6 m 70 m (for solids)