The "relays/controls" menu
73
L00-FMU90xxx-19-00-00-yy-061
A: switch on point; B: switch off point; C: relay energized; D: relay de-energized
tendency/speed
This limit type is similar to the "standard" type. The only difference is that variations with time of
the measured value are examined instead of the measured value itself. Therefore, the unit for the
switching points is "measuring value unit per minute".
inband
For this limit type, an upper and a lower switching point have to be defined.
The relay is energized if the measured value is between the two switching points.
The relay is de-energized if the measured value is above the upper or below the lower switching
point.
Additionally, a hysteresis can be defined, which affects both switching points.
out of band
For this limit type, an upper and a lower switching point have to be defined.
The relay is energized if the measured value is above the upper or below the lower switching
point.
The relay is de-energized if the measured value is between the two switching points.
Additionally, a hysteresis can be defined, which affects both switching points.
m, ft, m /h, ft /s, °C, m/min, ft/min,
33
t
t
A
B
C
D
t
t
B
A
C
D
m, ft, m /h, ft /s, °C, m/min, ft/min,
33