The "output/calculations" menu (for Profibus DP instruments)
134
7.2 "digital input" (DI)
7.2.1 "output calculations"
Use this list to select the DI block you are going to configure.
7.2.2 "digital input N" (N = 1 - 10)
"allocation"
Use this parameter to select a switching state. Occurrence of this state will be indicated by the DI
block.
Selection
relay
The DI block is connected to one of the relays of the instrument. After selection of this option,
the "relay" function appears, where you can select one of the relays.
pump control N (N = 1 or 2)
is only available if a pump control has been configured. After selection of this option, an additional
selection list appears which is used to allocate the DI block to one of the pump relays.
rake control
is only available if a rake control has been configured. After selection of this option, an additional
selection list appears, which is used to allocate the DI block to the rake control relay.
none
No value is transferred via the DI block.
"value"
Displays the current switching state of the selected relay.
"status"
Displays the status which is transferred with the binary value.
output/calculat. 01000
analog input
digital input
Profibus DP
output/calculat. 0XB01
digital input 1
digital input 2
digital input 3
digital input 4
digital input 1 O1B03
allocation:
value:
status: