The "relays/controls" menu
78
"start counter" and "stop counter"
You can use these parameters to exclude very small and very large flows from being counted.
If the flow is below "start counter" or above "stop counter" no pulses are generated. Both values are
to be specified as a percentage of the maximum flow (Q
max
).
• Default of "start counter": 0%
• Default of "stop counter": 100%
L00-FMU90xxx-19-00-00-yy-065
A: start counter; B: stop counter; C: relay energized; D: relay de-energized
5.1.7 "relay N" (N = 1 ...6)
(Parametrization of an alarm relay)
For an alarm relay, no additional parameters are required. Press "→" in order to proceed to the next
parameter set.
t
100%
t
A
B
C
D
0%
⇒
relay 2 R2103
function: alarm